Comes complete with a calibration Certificate Traceable to National Standards when purchased new.
The HPAT600/2 HandyPAT is an easy to use battery powered, hand held PAT tester that is ideal for testing all types of portable appliances. Supplied with rechargeable batteries for low running costs, a mains and in-car charger for convenience. Whilst recharging, it can still be operated from the mains supply ensuring maximum productivity at all times.
It has a fast automatic one button test sequence or a simple to operate manual mode useful for diagnostics and can be used for testing both 240V and 110V appliances with the optional TL157 adaptor lead.
In automatic mode, the HPAT600/2 will routinely run through a selected test sequence without any further user interaction unless a failure is encountered. In manual mode, a connection diagram for the selected test type is shown on the display and each step of a test requires user confirmation by a press of the OK button.
The user can select either the standard 500V insulation test or a 250V option which is required for testing appliances with surge protected circuits. The pass levels can also be adjusted which is particularly useful for testing appliances with long power cords or long extension leads.
With the ability to store test data for up to 200 appliances for on-screen recall, makes it easy to review earlier results when on-site. This function is not for downloading to a PC.
In addition to the mandatory safety tests, it can also be used to carry out a simulated load test to check the appliance is in working order and to confirm the integrity of the fuse.
Specifications:
Earth continuity |
Test current: 200mA DC Range: 0-19.99Ω Resolution: 0.01Ω Accuracy: ± (5% rdg + 2 dgt) Default pass level: Class I ≤ 0.1Ω, Lead ≤ 0.1Ω User selectable pass levels: 0.1Ω to 0.9Ω in 0.1 steps |
Insulation |
Test Voltage: 250V/500V DC selectable Test current: 1.5mA Ranges: 2.00MΩ, 20.0MΩ, 200MΩ Resolution: 0.01MΩ Accuracy: <100MΩ ± (5% rdg + 2 dgt), >100MΩ ± (10% rdg + 2 dgt) |
Default pass level |
Lead: ≥ 1.0 MΩ Class I: ≥ 1.0 MΩ Class II: ≥ 2.0 MΩ |
User selectable pass level |
0.3MΩ to 1MΩ in 0.1MΩ steps 1MΩ to 10MΩ in 1MΩ steps |
Fuse test |
Voltage: 4V DC (open circuit) Current: 200mA DC (short circuit) Pass level: >2mA |
Simulated load test |
Voltage: 4V DC (open circuit) Current: 200mA DC (short circuit) Accuracy: ± (5% rdg + 2 dgt) |
Overload protection |
300V AC/DC |
Complies with |
BS EN 61010 |
Temperature range |
-10 to 40°C |
Supply |
6 x 1.2V AA NiMH rechargeable batteries 1800mAh |
Dimensions |
90 x 210 x 54mm |
Weight |
700g (inc batteries & leads) |
Includes |
TC57 carry case, PSUHPAT230 mains charger, rechargeable batteries, EX332 IEC lead, TL67 earth bond probe, PSUHPAT12 in-car charger, earth null adaptor and manual |
Included
A comprehensive range of optional adaptor leads are available enabling 110V appliance testing and testing of equipment terminated with 3 phase plugs.
HPAT600/2 PAT tester comes complete with a Calibration Certificate Traceable to National Standards when purchased new.
Contact us for further information regarding HPAT600/2 PAT tester.