Chauvin Arnoux CA5273

Chauvin Arnoux CA5273 Digital Multimeter

Chauvin Arnoux CA6460 Earth Ground Tester

Chauvin Arnoux CA6460 Earth Ground Tester

Chauvin Arnoux MTX 3297Ex ATEX Multimeter

£1,508.40 £1,257.00
Availability: In stock
SKU
MTX3297

Metrix MTX 3297Ex ATEX Multimeter

Highlights

  • Certified ATEX/IEC Ex IIC (gas) 0, 1, 2, IIIC (dust) 20, 21, 22 and Mines M1
  • TRMS AC+DC acquisition
  • 60,000-count display resolution
  • 100 kHz bandwidth
  • 1µV resolution for voltage and 0.01 µA resolution for current
  • Large 5.7'' backlit digital screen
  • Secure terminal strip with clear indication of the connections to avoid any risk of error

Out of operation / Non-Ex:

  • 1000 V CAT III / 600 V CAT IV
  • IP67

ATEX Ex IECEx IEC61010-2-033 1000V_CAT_III 600V_CAT_IV IP67

Metrix MTX 3297 Ex ATEX Multimeter comes complete with a calibration Certificate Traceable to National Standards when purchased new.

Contact us for further information regarding Metrix MTX 3297 Ex ATEX Multimeter

Description

MTX 3297Ex is ideal for your electrical measurement work in explosive Ex zones (mines, presence of gas, in presence of explosive dust).  Approved and certified for the highest levels of risk.  A multimeter which meets the strictest requirements.

The MTX 3297Ex is certified as EX and IECEx for the following zones:

  • IIC (gas) 0,1 and 2
  • IIIC (dust) 20, 21 and 22
  • Mines M1

The MTX 3297Ex is a digital multimeter which complies with European directive 2014/34/UE on explosive (Ex) atmospheres. The MTX 3297Ex fulfils all the requirements related to the operating constraints in sectors such as:

  • the oil industry
  • the chemicals industry
  • argri-food
  • the pharmaceutical industry
  • the cosmetics industry
  • cement production
  • mining, etc.

It meets the needs of electrical maintenance teams: tests and troubleshooting inside and outside any hazardous zones with explosive atmospheres, without sacrificing compliance or measurement performance.

Usable outside Ex zones (out of operation), whatever the industrial activity, is high-performance industrial multimeter complaint with the IEC 61010-2-033 standard for work on 1000 V CAT III / 600 V CAT IV electrical installations.  The MTX 3297Ex is a communicating instrument offering optimum industrial performance. It is possible to record the measurements on a PC by means of the SX-DMM software available for download from Chauvin Arnoux website free of charge.

Measurements

  • Voltage
  • Current
  • Resistance (continuity, semiconductor junction)
  • Capacitance
  • Frequency (duty cycle/pulse width)
  • Temperature
  • AC/DC current measurement with selection of the I/O ratio

Functions

Specific measurements:

  • VLowZlow-impedance voltage measurement in the presence of "stray" disturbance voltages.
  • Low-pass filter for measuring the PWM signal

Functions to help with analysis and diagnostics

  • Min, MAX, Peak+ and Peak- functions
  • ∆X differential and ∆X/X relative functions
  • Duty cycle and pulse width
What’s Included:

Intrinsic safety

  • MTX 3297 Ex multimeter
  • 1 set of 2 straight / elbow cables 1.5m long
  • 1 set of test probes
  • Quick Start Guide in 18 languages
  • Safety manual
  • 1 set of 4 x 1.5V AA batteries/FR6 Li-FeS2 Ex/IEC Ex-qualified batteries (pre-installed in the instrument)

Use outside Ex Zones

  • Optical / USB cable
  • Carrying bag
Specifications
DC, AC, V AC + DC Voltages
V DC Measurement range 0.001 mV to 1000.0 V DC
Accuracy 0.05%  +25 digits
V AC, V AC + DC Measurement range 0.001 mV to 1000.0 V AC or AC+DC
Accuracy / bandwidth 0.05%  +25 digits. 0.05% +40 digits /100 kHz
Vlowz Measurement range 0.01mV to 1000.0 V
Accuracy / bandwidth 0.05% +25 digits / 300 Hz
Qualified measurement range in Ex zones 0.001 mV to 65.00 V
DC, AC, V AC + DC currents (protected by fuse)
A DC Measurement range 0.01 uA to 10.00 A DC (max 20 A/30 s)
Accuracy 0.8%  +20 digits
A AC, A AC + DC Measurement range 0.01 uA to 10.00 A AC or AC + DC (max 20 A/30 s)
Accuracy / bandwidth 1.0%  +25 digits / 20 kHz
Qualified measurement range in Ex zones 0.01 uA to 5.00 A
with external sensor (clamp) up to 6,000 A depending on sensor, transformation ratio 1, 10, 100, 1,000 mv/A
Frequency
Hz Measurement range 10.00 Hz to 200.0 kHz (for V), 20.00 kHz (for A)
Accuracy 0.1%  +1 digit
Resistance & Continuity, Diode
Ω Measurement range 0.00 Ω to 60.000 MΩ
Accuracy 0.1% +20 digits
Continuity Audible signal <30 + 5 Ω / <5 V,I <1.1mA
Diode Test 3.000 V, 1% +30 digits / U <5 V,I<1.1mA
Capacitance
nF, uF, mF Measurement range 0.100 nF to 60.000 mF
Accuracy 1% +10 digits
Temperature PT100/PT1000
°C/°F Measurement range -200.0 °C to 800.0°C
Accuracy 0.1% ± 1.5°C
Other measurements 
Secondary measurements Duty cycle, pulse width, resistive power (U2/R), dBm
Functions
Max/Min/Avg, Peak+/Peak- 100 ms on all the main measurements except Peak (1 mS)
ΔREL, ΔREL/R Differential value, relative value
PWM filter 4th-order 300 Hz low pass filter
General specifactions
Display Double 60,000-count LCD screen with 3 level backlighting
Power supply 4 x AA/FR6 Li-FeS2 Ex-qualified batteries / Battery life 350 h
Compliance outside Ex zones IEC 61010-2-033 1000V CATIII/600V CAT IV, EN61326-1 Class B
Ingress protection / Environment IP 67 / Storage -20°C to 70°C, Use -10°C to +55°C
Mechanical specifications Dimensions (LxWxH) 196 x 90 x 47.1 mm Weight 715g